Vibronic Point Level Detection Nivotester FailSafe FTL825

Brand: Endress+Hauser

Vibronic Point Level Detection Nivotester FailSafe FTL825

Brand: Endress+Hauser
Xpert Xpert

The Nivotester FTL825 supplies the Liquiphant FailSafe FTL8x point level switch with direct voltage via a two-wire cable. At the same time, it analyzes the current values (4-20mA discrete) of the Liquiphant and returns a switching signal. The signal inputs of the Nivotester FTL825 are galvanically isolated from the mains and the output and can be ordered Safety-critical systems up to SIL3. For industries where redundant or diverse systems are either not recommended or not possible.

  • Ambient temperature: -20 to +60°C (-4 to +140°F)
  • International explosion protection certificates, overfill prevention WHG
Features
  • Use in safety systems requiring functional safety to SIL3 in accordance withIEC 61508 Ed.2.0 /IEC 61511-1 / ISA 84-1
  • Proof test: proof testing interval up to 12 years, Slave devices tested at the press of a button
  • For safety-critical systems up to SIL3 in the chemicals, petrochemicals and oil & gas industries
  • For applications where redundant or diverse systems are either not recommended or not possible, the longest possible test cycles are desirable, or proof tests are either not possible or only with great difficulty and expense
  • Integrated locking function (self-holding)
  • 4 switching outputs (can be analyzed separately): 2 as level safety contacts based on the quiescent current principle for a redundant output signal, 1 x signaling contact (e.g. lamp),1 x fault-signaling contact as changeover contact

Specifications

Measuring Principle

  • Vibration Liquids

Characteristic / Application

  • FailSafe level transmitter point level.
  • Top hat rail mounting
  • Connection to FTL80/81/85
  • Permanent self-monitoring,LIVE-Signal.

Specialities

  • SIL 3 according to IEC61508.

Supply / Communication

  • 85 - 253 VAC/DC
  • 20 - 30 VAC/20-60VDC

Ambient Temperature

  • –20 to +60 °C
  • (–4 to +140 °F)

Communication

  • 2x SPST safety contact point level
  • 1x SPST signal contact
  • 1X SPDT fault contact

Certificates / Approvals

  • ATEX, FM, CSA, CSA C/US, IEC Ex, NEPSI

Safety Approvals

  • Overfill protection WHG
  • Leakage Detection

Marine Approvals

  • GL/ ABS/ LR/ BV/ DNV
show more