Vibronic Point Level Detection Liquiphant FTL81

Brand: Endress+Hauser

Vibronic Point Level Detection Liquiphant FTL81

Brand: Endress+Hauser
Xpert Xpert

Liquiphant FTL81 is a point level switch for use in hazardous areas with all international certificates. FailSafe overfill protection in applications with functional safety up to SIL3 with one device. Reliable measurement values, not affected by: changing media properties, flow, turbulences, gas bubbles, foam, vibrations, or build-up.

  • Process connections: Threads and flanges
  • Temperature: -60 to +280°C (-76 to +540°F)
  • Pressure: -1 to +100bar (-14.5 to +1,450psi)
  • Sensor length: Extension pipe up to 3m (9.8ft)
  • Sensor material: 316L, Alloy C
  • International explosion protection certificates, overfill protection WHG, SIL, marine approvals
Features
  • Use in safety systems requiring functional safety to SIL3 in accordance with DIN EN IEC 61508 Ed.2.0 and DIN EN ISO 13849
  • Proof test: proof testing interval up to 12 years, Slave devices tested at the press of a button
  • Permanent self-monitoring/internal redundancy
  • 4-20mA interface (acc. to NAMUR NE 06/NE 43): easy integration via the switching unit (Nivotester FailSafe FTL825) with a two-channel output (safety contacts) and locking function or direct integration into a safety PLC
  • No adjustment: quick, low-cost startup
  • No mechanically moving parts: no maintenance, no wear, long operating life
  • Monitoring of fork for damage, corrosion, build-up and mechanical blocking

Specifications

Measuring Principle

  • Vibration Liquids

Characteristic / Application

  • Reliable point level switch with extension pipe for MIN and MAX safety applications up to SIL3.
  • Dual Sealing / Second line of defense
  • Modular housing concept

Specialities

  • Permanent LIVE signal
  • Monitors function safety
  • Failsafe design and
  • High availability of the measuring values

Supply / Communication

  • 2-wire 4...20 mA

Ambient Temperature

  • -60°C...+70°C
  • (-76°F...+160°F)

Process Temperature

  • -60°C...+280°C
  • (-76°F...+540°F)

Process Pressure / Max. Overpressure Limit

  • Vacuum...100 bar
  • (1450 psi)

Min. Density of Medium

  • Density from 0.4 g/cm3
  • (0.4 SGU)

Main Wetted Parts

  • 316L
  • Alloy C

Process Connection

  • Flange: DN25...DN100,
  • Flange: ASME 1"...4",
  • Flange: JIS 10K...20K
  • Thread: G3/4, G1, R3/4,
  • Thread: R1, MNPT3/4, MNPT1

Sensor Length

  • Extension pipe up to 3 m (9.8 ft)

Communication

  • 2-wire 4...20 mA

Certificates / Approvals

  • ATEX, FM, CSA, CSA C/US, IEC Ex, NEPSI, EAC

Safety Approvals

  • Overfill protection WHG
  • Leakage Detection
  • SIL3

Design Approvals

  • EN 10204-3.1
  • NACE MR0175, MR0103
  • ASME B31.3
  • AD2000

Marine Approval

  • GL/ ABS/ LR/ BV/ DNV

Options

  • PWIS free
  • Pressure tight feed through
  • Weather protection

Components

  • Nivotester FTL825, Transmitter
show more