Liquiphant FTL62 Point Level Switch
Brand: Endress+HauserLiquiphant FTL62 Point Level Switch
Brand: Endress+Hauser
Liquiphant FTL62 has a strong focus on specific applications with aggressive liquids and simplicity with easy proof testing, reliability and safety (SIL) with compliance to IEC 61508, API 2350 and WHG.
The vibronic device is determined for a safe and active measuring technology in aggressive liquids and want a reliable and proven point level detection for tank overfill protection and pump dry run protection.
The FTL62 is easy to use, has a digital connection and gives a real-time data at hand.
Point level switch with extension tube for pumpable liquids.
- Coated sensor for aggressive media: ECTFE (Halar), PFA (EdlonTM, Ruby Red, conductive), Enamel
- Process temperature: -60 °C to +150°C
- Process pressure: -1 to +40bar
- Ambient temperature: -60 to +70°C
- Viscosity up to 10,000 mm2/s (cSt)
- Process connections: Flanges
- International explosion protection certificates, overfill protection WHG, SIL, marine approvals
- Universal measuring principle for limit detection – proven vibronic technology
- Developed according IEC 61508 for highest safety – SIL2/3 applications (3rd party approved)
- Periodic proof testing is quickly and simple organized with guided wizards via the SmartBlue-App or via a test button or magnetic pin from outside. Via digital communication you can initiate the device for a fast and easy testing of the safety loop.
- Heartbeat Technology allows safe, continuous diagnostics and a simple verification, without process interruption
- Centralized asset management with easy online access to all device information thanks to digital communication
- Second line of defense to protect the environment
Specifications
Brand
Measuring Principle
- Vibration Liquids
Characteristic / Application
- Compact vibronic device with highly corrosion-resistant coating for aggressive media
- Optional extension tube up to 3 m (9.8ft)
- Modular housing concept
Specialities
- Heartbeat Technology
- Bluetooth® Operation and maintenance SmartBlue App
- LED Module
- RFID TAG for easy identification
- Second line of defense
- Temperature spacer for high process temperature
- Plug and play functionalities
Supply / Communication
- 19...253 VAC / 2-wire
- 10...55V / DC-PNP 3-wire
- 9...20 VDC with relay DPDT
- 19...253 VAC or 19...55 VDC with relay DPDT
- 2-wire NAMUR
- 2-wire PFM
- 4-20mA HART
Ambient Temperature
- -60 °C...+70 °C (-76 °F...+158 °F)
Process Temperature
- -50 °C...+150 °C (-58 °F...+302 °F)
Process Pressure / Max. Overpressure Limit
- Vacuum...40 bar
- Vacuum...580 psi
Min. Density of Medium
- 0.5 g/cm³
- 0.4 g/cm³ optional
Main Wetted Parts
- ECTFE
- PFA (Edlon, RubyRed or conductive)
- 316L
- Enamel
Process Connection (Flange)
- DN25...DN100
- ASME 1"...4"
- JIS 50A
Sensor Length
- Up to 3 m (9.8 ft)
Communication
- 2-wire direct load
- HART
- DC-PNP 3-wire
- Relays
- NAMUR
- PFM
- Bluetooth® wireless technology
Certificates / Approvals
- ATEX, IEC Ex, NEPSI, EAC Ex, KC, JPN Ex, INMETRO, UK Ex
Safety Approvals
- Overfill protection WHG
- SIL2/ SIL 3 according to IEC 61508
Design Approvals
- EN 10204-3.1
- ASME B31.3 Process Piping
- CRN
Marine Approval
- ABS/ LR/ BV/ DNV
Options
- Ambient temperature down to -60 °C (-76 °F)
- Heavy duty stainless steel housing
Components
- FTL325P Interface PFM
- FTL325N Interface NAMUR