Vibronic Point Level Detection Nivotester FTL325N

Brand: Endress+Hauser

Vibronic Point Level Detection Nivotester FTL325N

Brand: Endress+Hauser
Extended Extended

Nivotester FTL325N is a switching unit for point-level detection in liquid tanks, also in hazardous explosion areas. Also suitable for overfill prevention in tanks with combustible or non-combustible liquids harmful to water. Two-point control and point-level detection. The perfect fit for applications in safety-related systems with requirements for functional safety up to SIL2 in accordance to IEC 61508 /IEC 61511 using Liquiphant with electronic insert FEL56 or FEL58.

  • Ambient temperature: -20 to +50°C (-4 to +122°F)
  • International explosion protection certificates, overfill prevention WHG, marine approvals
Features
  • Nivotester FTL325N for connecting one, two or three measuring cells (1-, 2- or 3-channel devices)
  • Intrinsically safe signal circuits Ex ia for use of measuring sensor in explosion hazardous areas
  • Functional safety up to SIL2 through line monitoring
  • DIN Rail housing for simple series installation on standard rails in switch cabinet
  • Simple wiring using pluggable terminal blocks
  • NAMUR interface to EN 50227 (DIN 19234; NAMUR) or IEC 60947-5-6 to connect NAMUR sensors or electronic inserts

Specifications

Measuring Principle

  • Vibration Liquids

Characteristic / Application

  • Switching unit NAMUR technology for rail mounting
  • SIL2, according 61511
  • Intrinsically safe

Supply / Communication

  • NAMUR
  • 24V AC,DC / 230V AC

Ambient Temperature Range

  • Single Installation: -20 °C ... 60 °C
  • Single Installation: (-4 °F ... 140 °F)
  • Rail Mounting: -20 °C ... 50 °C
  • Rail Mounting: (-4 °F ... 122 °F)

Communication

  • 1 Channel: 1 level SPDT + 1 alarm SPST
  • 3 Channel: 3 level SPDT + 1 alarm SPST

Certificates / Approvals

  • ATEX, FM, CSA, IEC Ex, INMETRO, NEPSI, EAC

Safety Approvals

  • Overfill prevention WHG
  • SIL
show more