Vibronic Point Level Detection Liquiphant FTL31
Brand: Endress+HauserVibronic Point Level Detection Liquiphant FTL31
Brand: Endress+Hauser
Liquiphant FTL31 is a point-level switch for liquids. The FTL31 is designed for industrial applications in all industries, mainly the machinery industry. The Liquiphant is used for overfill protection or pump dry-run protection in cleaning systems. The IO-Link capability allows easy parameter setting.
Compact: - Smallest vibronic sensor in the market
Safe: Continuous self-monitoring Reliable switching independent of media properties
Easy: - No calibration - Plug & play - IO-Link connectivity
- Process connections: Threads
- Temperature: -40 to +150°C (-40 to +302°F)
- Pressure: -1 to +40bar (-14.5 to 580psi)
- Surface roughness: 3.2µm
- Overfill protection and leakage detection WHG, marine approvals, final inspection report
- Designed according to the highest requirements for quality and environmental sustainability. The self-monitoring Liquiphant offers safe switching also in case of power supply loss.
- Independent of changing media properties, an accurate switching point is offered. IO-Link reduces costs and complexity due to easy configuration of the devices via engineering tools
- A real plug & play sensor is offered without any need for adjustment, even with changing media. Measurement is unaffected by conductivity, build-up, turbulence, flows or air bubbles
- No calibration is required, no specific know-how or tools (e.g. software) necessary
- Robust design made of stainless steel (316L) assures highest durability
- A modular design offers different process temperatures and the widest variety of process connections and accessories in the market to fit every application
- No mechanically moved parts, free of maintenance
Specifications
Brand
Measuring Principle
- Vibration Liquids
Characteristic / Application
- Level switch for liquids and is used in tanks, vessels
- and pipes.
Supply / Communication
- 20 ... 253V AC/DC, 2-wire
- 10 ... 30V DC-PNP 3-wire
Ambient Temperature
- -40 °C ... 70 °C
- (-40 °F ... 158 °F)
Process Temperature
- -40 °C ... 150 °C
- (-40 °F ... 302 °F)
Process Pressure / Max. Overpressure Limit
- Vacuum ... 40 bar
- (Vacuum ... 580 psi)
Min. Density of Medium
- >0,7g/cm³
- (>0,5g/cm³ optional)
Main Wetted Parts
- 316L
Process Connection
- G1/2, G3/4, G1, MNPT1/2, MNPT3/4, MNPT1, R1/2, R3/4, R1
Communication
- AC/DC, DC-PNP
Certificates / Approvals
- CSA C/US, EAC
Safety Approvals
- Overfill protection WHG
- Leakage
Design Approvals
- EN 10204-3.1
Marine Approval
- ABS/ LR/ BV/ DNV
Options
- Adjustment switching delay
- Cleaned from oil+grease
- PWIS free