iTEMP TMT84 Temperature Transmitter

Brand: Endress+Hauser

iTEMP TMT84 Temperature Transmitter

Brand: Endress+Hauser
Extended Extended

Unsurpassed reliability, accuracy and long-term stability in critical processes over all industries. The configurable transmitter not only transfers digital converted signals from RTD and TC sensors, it also transfers resistance and voltage signals using PROFIBUS® PA communication. High measurement point availability by means of sensor monitoring functions. Diagnostics information according to NAMUR NE 107. Optimization of the measurement accuracy by sensor-transmitter matching.

  • 2 input channels and PROFIBUS® PA protocol for the conversion of input signals into digital output signals
  • The device stands out due to signal reliability, long-term stability, high precision and advanced diagnostics (important in critical processes)
  • For the highest level of safety, availability and risk reduction
  • Installation in flat-face terminal head as per DIN EN 50446
  • Optional installation in field housings even for use in Ex d areas - with mounting brackets for wall or pipe mounting
Features
  • Easy and standardized communication via PROFIBUS® PA Profile 3.02
  • Meets the EMC requirements as per NAMUR NE 21 and the recommendations of NE 89 with regard to temperature transmitters with digital signal processing
  • Straightforward design of measuring points in Ex-areas through FISCO/FNICO conformity in accordance with IEC 600079-27
  • Safe operation in hazardous areas thanks to international approvals such as FM IS, NI, CSA IS, NI as well as ATEX Ex ia, Ex nA (Ex nL)
  • High accuracy through sensor-transmitter matching
  • Reliable operation with sensor monitoring and device hardware fault recognition
  • Rapid no-tools wiring due to optional spring terminal technology

Specifications

Measuring Principle

  • Head transmitter

Input

  • 2 x RTD, TC, Ohm, mV

Output

  • PROFIBUS PA

Auxiliary Power Supply

  • 9...32 VDC (PROFIBUS PA)
  • 9...17.5 VDC (FISCO/FNICO)

Communication

  • PROFIBUS PA

Installation

  • Terminal head form B

Accuracy

  • (Pt100) <= 0.1 K
  • (Pt100) <= 0.18 °F

Galvanic Isolation

  • yes

Certification

  • ATEX II3G Ex ic IIC T6 Gc
  • ATEX II2D Ex tb IIIC Db
  • ATEX II1G Ex ia IIC T4/T5/T6
  • ATEX II3G Ex nA IIC T6 Gc
  • ATEX II3D Ex tc IIIC Dc
  • ATEX II1G Ex ia IIC T6 Ga, II3D
  • ATEX II3G Ex nA IIC T6 Gc, II3D
  • ATEX II2G Ex d T6, II2D Ex tb IIIC
  • FM+CSA IS, NI I/1+2/ABCD
  • CSA C/US General Purpose
  • FM IS, NI I/1+2/ABCD
  • CSA IS, NI I/1+2/ABCD
  • CSA XP, NI, DIP I, II, III/1+2/A-G
  • NEPSI Ex ia IIC T4/T5/T6
  • TIIS Ex ia IIC T6
  • NEPSI Ex nA IIC T4/T5/T6
  • IECEx Ex ia IIC T4/T5/T6
  • FM XP, NI, DIP I, II, III/1+2/A-G
  • EAC Ex ia IIC T6 Ga
  • EAC Ex d IIC T6 Gb
  • IECEx Ex tb IIIC Db
  • IECEx Ex d T6 Gb, Ex tb IIIC Db
  • INMETRO Ex ia [ia Ga] IIC T6 Gb
  • INMETRO Ex d T6 Gb, Ex tb IIIC Db
  • NEPSI Ex d IIC T6 Gb
  • UK II2D Ex tb IIIC Db
  • UK II3D Ex tc IIIC Dc
  • UK II1G Ex ia IIC T6 Ga, II3D Ex ia IIIC Dc
  • UK II3G Ex nA IIC Gc, II3D Ex tc IIIC Dc
  • UK II2G Ex db IIC T6 Gb, II2D Ex tb IIIC Db
  • ATEX IECEx II1G Ex ia IIC T6 Ga
show more