FieldPort SWA50
Brand: Endress+HauserFieldPort SWA50
Brand: Endress+Hauser
The FieldPort SWA50 converts the HART signal of the connected HART field device to a reliable and encrypted Bluetooth® or WirelessHART signal. The Endress+Hauser SmartBlue app or the Endress+Hauser Field Xpert is used to configure the FieldPort SWA50 and to visualize the measured values and status of the connected HART field device. HART field devices can be connected to the Netilion Cloud via the FieldPort SWA50 and a FieldEdge device.
The FieldPort can be retrofitted to all 2-wire and 4-wire HART field devices in both hazardous and non-hazardous areas. The robust stainless steel housing allows the FieldPort SWA50 to be installed even in harsh industrial environments.
Features- Reliable transmission of the measured process values through the connected FieldPort SWA50 via encrypted Bluetooth® or WirelessHART communication
- Easy to retrofit all 2-wire or 4-wire HART field devices
- Easy connection of all HART field devices to theNetilion Cloud
- Loop-powered adapter, without affecting the process signal
- Easily accessible, wireless, diagnostic information of connected HART field device
Specifications
Brand
Measuring Principle
- WirelessHART
Function
- Intelligent WirelessHART and/or Bluetooth® interface module for easy and fast connection to HART devices
Certification
- Non-hazardous area, ATEX, IEC Ex
Input
- One point-to-point with HART device
Output
- Transmission range under reference conditions: WirelessHART communication - up to 200 m (656 ft); Bluetooth communication - up to 40 m (131 ft)
- WirelessHART and/or Bluetooth® communication interface
- Operating frequency: 2.4 GHz (ISM band)
Auxiliary Power Supply / Loop Power Supply
- Loop-powered 4 to 20 mA
Dimensions (W x H x D)
- 146 mm x 42 mm x 42 mm
- (dimensions in mm 25.4 = 1 inch)
Software
- Internal software for reading data from HART field devices and communicating over WirelessHART and/or Bluetooth®
Operation
- Integral via DIP-switches
- Cell Phone configuration via SmartBlue App and Bluetooth®
- Field Xpert configuration via Bluetooth® or HART-modem
- PC configuration via FieldCare and HART-modem
- PC configuration via FieldCare and WirelessHART Gateway
Operating Voltage
- 24 VDC (min. 4 VDC, max. 30 VDC): min. 3.6 mA loop current required for start-up
- Voltage drop if internal HART communication resistor is deactivated: 3.2 V in operation, < 3.8 V at start-up
- Voltage drop if internal HART communication resistor is activated (270 Ohm): < 4.2 V at 3.6 mA loop current, < 9.3 V at 22.5 mA loop current