Cerabar PMP43 Hygienic Pressure Transmitter
Brand: Endress+HauserCerabar PMP43 Hygienic Pressure Transmitter
Brand: Endress+HauserThe Cerabar PMP43 is a pressure transmitter and part of the Compact Line. The product line is especially developed for hygienic applications and combines a compact design with full performance. The proven technology is suitable for the measurement and monitoring of absolute and gauge pressure in liquids and gases. Thanks to the compact sensor design and small process connections, the device is flexible in scale and can be installed in tight space conditions.
Cerabar PMP43 is used for the measurement of pressure and level in pipelines as well as in process and storage tanks.
The Cerabar PMP43 is suitable for a wide range of hygienic applications:
- Pressure monitoring of process pipes
- Hydrostatic level measurement in process tanks/pressurized tanks
- Pressure monitoring in narrow skids and modules
- Outstanding ease of use due to easy setup and operation with guided wizards and intuitive touch display
- Improved process and product safety through configuration integrity - a checksum algorithm (CRC) ensures that safety relevant parameters remain unchanged
- Increased productivity thanks to traceable and documented on-demand verification without process interruption and permanent monitoring of process anomalies or blocked impulse lines with Heartbeat Technology
- 360-degree hygienic design and IP69 ingress protection class enable efficient cleaning and avoid contamination
- Documented compliance through certified hygienic design as well as proven material conformity and traceability
Specifications
Brand
Measuring Principle
- Absolute and gauge pressure
Characteristic
- Pressure transmitter with metal membrane for accurate measurement in liquids or gases
- Designed for hygienic applications
- Available with diaphragm seals
Supply Voltage
- 4...20mA HART
- 11.5...45 VDC (Non Ex): Ex ia: 11.5...30 VDC
Reference Accuracy
- Standard 0.1%
- Platinum 0.075%
Long Term Stability
- 0.1% of URL/year
- 0.2% of URL/ 5 years
- 0.25% of URL/ 10 years
Process Temperature
- -40°C...+130°C (-40°F...+266°F)
- -20°C...+200°C (-4°F...+392°F)
Ambient Temperature
- -40°C...+85°C
- -40°F...+185°F
Measuring Cell
- 400 mbar...100 bar
- 6 psi...1450 psi
Smallest Calibratable Span
- 20 mbar (0.3 psi)
Vacuum Resistance
- 50 mbar (0.725 psi)
Max. Turn Down
- 20:1
Process Connection
- Thread: G1/2...G2, R1/2, MNPT3/4...MNPT2,FNPT1/2
- Flange: DN25...DN80, NPS 1"...3"
Process Connection Hygienic
- Tri-Clamp
- DIN11851
- DIN11864-1
- NEUMO
- Varivent
- SMS
- DRD
- Universal adapter
Material Process Membrane
- 316L
Material Gasket
- None, diaphragm welded
Material Housing
- 316L hygiene
Communication
- 4...20 mA
- 4...20 mA HART
- 4...20 mA IO-Link
Certificates / Approvals
- ATEX, FM, CSA, CSA C/US, IECEx, INMETRO, NEPSI, UK Ex
Design Approvals
- EN10204-3.1
- NACE MR0175
Hygienic Approvals
- CoC ASME-BPE
- 3A
- EHEDG
Drinking Water Approvals
- NSF/ANSI 61
- ACS
- KTW