RN22 Active Barrier

Brand: Endress+Hauser

RN22 Active Barrier

Brand: Endress+Hauser

Local Support: Authorized Distributor Serving Alabama, Mississippi, Louisiana, Florida, New York, Connecticut, Massachusetts, Vermont, New Hampshire, Maine, Rhode Island, Puerto Rico, US Virgin Islands and parts of Tennessee and Arkansas.

Fundamental Fundamental

The 1- or 2-channel RN22 active barrier powers analog instrument loops and safety instrumented systems up to SIL 2 (SC 3). The intrinsically safe, HART ® transparent interface establishes a reliable link between field devices and process control. It interfaces with 2-/4-wire devices in hazardous areas and provides a second galvanically isolated signal output acc. to NAMUR NE 175 . This opens a second channel for the process optimization domain without affecting the traditional automation system.

  • Single- or two-channel active barrier, power supply or signal doubler
  • 0/4 to 20 mA analog signal transmission (NAMUR NE 43) and galvanic isolation
  • Intrinsic safety for operation in hazardous areas (Zone 2)
  • Bidirectional HART® communication (transparent)
  • 2- and 4-wire capability for instruments in hazardous areas (Zones 0/20)
  • Ambient temperature range: -40 … 60 °C (-40 … 140 °F)
Features
  • Intrinsically safe interface device suited for use in safety instrumented systems up to SIL 2 (SC 3) in accordance with IEC 61508
  • Quick and easy wiring with screw or push-in terminals or power supply via power rail T-connector
  • Easy access to frontside HART® connection taps
  • Compact housing: up to two channels on 12.5 mm (0.49 in) for efficient use of space in control cabinets

Specifications

Measuring Principle

  • Active Barrier

Function

  • 1-channel
  • 2-channel
  • Signal doubler

Loop Power Supply

  • 17.5 V ±1 V bei 20 mA open circuit
  • voltage: 24.5 V ±5 %

Power Supply

  • 24 VDC

Input

  • 0/4…20 mA / HART
  • feeding/not feeding

Output

  • 0/4…20 mA / HART
  • active/passive

Certificates

  • ATEX II3G Ex tc IIIC Dc
  • CSA C/US AIS, I/2/ABCD
  • EAC [Ex ia Ga] IIC, [Ex ia Da] IIIC, Ex ec IIC Gc
  • JPN [Ex ia Ga] IIC, [Ex ia Da] IIIC, Ex ec IIC Gc
  • KC [Ex ia Ga] IIC,[Ex ia Da] IIIC, Ex ec IIC Gc
  • INMETRO [Ex ia Ga] IIC,[Ex ia Da] IIIC, Ex ec IIC Gc
  • NEPSI [Ex ia Ga] IIC, [Ex ia Da] IIIC, Ex ec IIC Gc
  • UK II3G Ex tc IIIC Dc
  • UK II(1)G [Ex ia Ga] IIC, II(1)D [Ex ia Da] IIIC, II3G Ex ec IIC Gc
  • ATEX IECEx II(1)G [Ex ia Ga] IIC, II(1)D [Ex ia Da] IIIC, II3G Ex ec IIC Gc
  • UL C/US
  • DNV

SIL

  • SIL 2 SC 3

Operation

  • HART
show more