RN22 Active Barrier
Brand: Endress+HauserRN22 Active Barrier
Brand: Endress+Hauser
The 1- or 2-channel RN22 active barrier powers analog instrument loops and safety instrumented systems up to SIL 2 (SC 3). The intrinsically safe, HART ® transparent interface establishes a reliable link between field devices and process control. It interfaces with 2-/4-wire devices in hazardous areas and provides a second galvanically isolated signal output acc. to NAMUR NE 175 . This opens a second channel for the process optimization domain without affecting the traditional automation system.
- Single- or two-channel active barrier, power supply or signal doubler
- 0/4 to 20 mA analog signal transmission (NAMUR NE 43) and galvanic isolation
- Intrinsic safety for operation in hazardous areas (Zone 2)
- Bidirectional HART® communication (transparent)
- 2- and 4-wire capability for instruments in hazardous areas (Zones 0/20)
- Ambient temperature range: -40 … 60 °C (-40 … 140 °F)
- Intrinsically safe interface device suited for use in safety instrumented systems up to SIL 2 (SC 3) in accordance with IEC 61508
- Quick and easy wiring with screw or push-in terminals or power supply via power rail T-connector
- Easy access to frontside HART® connection taps
- Compact housing: up to two channels on 12.5 mm (0.49 in) for efficient use of space in control cabinets
Specifications
Brand
Measuring Principle
- Active barrier
Function
- 1-channel
- 2-channel
- Signal doubler
Loop Power Supply
- 17.5 V ±1 V bei 20 mA open circuit
- voltage: 24.5 V ±5 %
Power Supply
- 24 VDC
Input
- 0/4…20 mA / HART
- feeding/not feeding
Output
- 0/4…20 mA / HART
- active/passive
Certificates
- ATEX II3G Ex tc IIIC Dc
- CSA C/US AIS, I/2/ABCD
- EAC [Ex ia Ga] IIC, [Ex ia Da] IIIC, Ex ec IIC Gc
- JPN [Ex ia Ga] IIC, [Ex ia Da] IIIC, Ex ec IIC Gc
- KC [Ex ia Ga] IIC,[Ex ia Da] IIIC, Ex ec IIC Gc
- INMETRO [Ex ia Ga] IIC,[Ex ia Da] IIIC, Ex ec IIC Gc
- NEPSI [Ex ia Ga] IIC, [Ex ia Da] IIIC, Ex ec IIC Gc
- UK II3G Ex tc IIIC Dc
- UK II(1)G [Ex ia Ga] IIC, II(1)D [Ex ia Da] IIIC, II3G Ex ec IIC Gc
- ATEX IECEx II(1)G [Ex ia Ga] IIC, II(1)D [Ex ia Da] IIIC, II3G Ex ec IIC Gc
- UL C/US
- DNV
SIL
- SIL 2 SC 3
Operation
- HART