Ultrasonic Measurement Time-of-Flight Prosonic FMU90

Brand: Endress+Hauser

Ultrasonic Measurement Time-of-Flight Prosonic FMU90

Brand: Endress+Hauser
Xpert Xpert

Prosonic FMU90 separated version with field housing or top hat rail housing for control cabinet instrumentation are suited for continuous, non-contact level measurement of fluids, pastes, sludge, and powdery to coarse bulk solids. Also, the flow measurement in open channels and weirs is possible as the simultaneous measurement of level and flow in a stormwater overflow basin with only 1 sensor. The system can accommodate up to 6 relays for tendency alarm, flow pulse output, or backwater/sludge alarm, available in either 1- or 2-channel versions.

Level measurement of fluids and bulk materials with 1 or 2 sensors for measuring up to 45m (148ft) and level limit detection. Pump control, rake control and as option: additional pump control function.

  • Calculations: Average, difference, sum
  • Application flow: Flow measurement in open channels and weirs with 1 or 2 sensors
  • Flow measurement with back-water or sludge detection
  • Up to 3 totalizers and 3 counters
  • Counting or time pulse output for control of external units
Features
  • Simple, menu-guided operation with 6-line plain text display, 15 languages selectable
  • Envelope curves on the display for quick and simple diagnosis
  • Easy operation, diagnosis and measuring point documentation with the supplied "FieldCare" operating program
  • Time-of-Flight correction via integrated or external temperature sensors
  • Linearisation (up to 32 points, freely configurable) for the most common flumes and weirs pre-programmed and selectable
  • Online calculation of the flume/weir flows via integrated flow curves
  • Automatic detection of the sensors FDU9x

Specifications

Measuring Principle

  • Ultrasonic

Characteristic / Application

  • Separated version with Field housing or top hat rail housing for control cabinet instrumentation, up to 6 relays for pump / rake / limit control, 1 or 2 channel version

Specialities

  • Protection Class IP 66 / NEMA 4x
  • automatic sensor recognition of FDU9x sensors
  • option: flow measurement for open channel and weirs or additional pump control functions

Supply / Communication

  • 90 ... 253 VAC
  • 10.5 ... 32 VDC
  • up to 2x 4...20mA HART
  • Profibus DP

Accuracy

  • +/- 2mm + 0.17% of measured distance

Ambient Temperature

  • -40 °C ... 60 °C
  • (-40 °F ... 140 °F)

Communication

  • up to 2x 4 ... 20 mA HART
  • Profibus DP

Certificates / Approvals

  • ATEX, CSA

Options

  • Illuminated display, 6 line graphic display with country specific menu guidance, on-site diagnosis with envelope curve on display

Components

  • Sensors FDU9x
show more