Conductive Point Level Detection Liquipoint FTW32

Brand: Endress+Hauser

Conductive Point Level Detection Liquipoint FTW32

Brand: Endress+Hauser

Local Support: Authorized Distributor Serving Alabama, Mississippi, Louisiana, Florida, New York, Connecticut, Massachusetts, Vermont, New Hampshire, Maine, Rhode Island, Puerto Rico, US Virgin Islands and parts of Tennessee and Arkansas.

Fundamental Fundamental

The Liquipoint FTW32 offers simple and safe point level detection in conductive liquids. It offers numerous measuring possibilities due to multipoint detection (up to 5 rods).

For use in conductive liquids (as of 10μS/cm). for overfill prevention, dry running protection, two-point control of pumps or multiple point detection.

  • Process connections: Threads
  • Sensor length: 0.25 to 15m (10 to 590")
  • Temperature: -40 to 70°C (-40 to 158°F)
  • Pressure: -1 to 10bar (-14.5 to 145psi)
  • International explosion protection certificates, overfill prevention and leakage detection certificate WHG
Features
  • Cost-effective probe for conductive liquids with detection of up to five point levels with one probe
  • No calibration required
  • Standard setting for the most common conductive liquids
  • No moving parts in the tank - long service life, reliable operation with no wear or blockages

Specifications

Product Family

  • Liquipoint

Measuring Principle

  • Conductive

Characteristic / Application

  • Compact rope probe with multi point detection possible up to 5 switch points. Simple rope shortening possible

Supply / Communication

  • DC PNP 10.8V ... 45V
  • Relay 20 ... 230 VAC
  • Relay 20 ... 55 VDC

Ambient Temperature

  • -40 °C ... 70 °C
  • -40 °F ... 158 °F

Process Temperature

  • -40 °C ... 70 °C
  • -40 °F ... 158 °F

Process Pressure / Max. Overpressure Limit

  • Vacuum ... 10 bar
  • Vacuum ... 145 psi

Min. Conductivity of Medium

  • 10 µS/cm

Main Wetted Parts

  • 316L, FEP, PPS

Max. Tensile Strength

  • 500 N

Process Connection

  • G 1-1/2
  • NPT1-1/2"

Sensor Length

  • 0.25m ... 15m
  • 10" ... 590"

Communication

  • DC PNP
  • Relay

Certificates / Approvals

  • ATEX, EAC Ex

Safety Approvals

  • Leakage Detection

Components

  • Transmitter: FTW325

Application Limits

  • Observe min. medium conductivity
show more