iTEMP TMT162 Temperature Transmitter
Brand: Endress+HauseriTEMP TMT162 Temperature Transmitter
Brand: Endress+Hauser
Unsurpassed reliability, accuracy and long-term stability in critical processes. The remote configurable transmitter transfers and monitors converted signals from RTD sensors and thermocouples as well as from resistance and voltage signals using selectively HART ® , FOUNDATION Fieldbus™-, PROFIBUS ® PA-communication. It visualizes the signals on its own backlit display. A field housing allows a direct connection in harsh process areas as well as in hygienic applications as option.
- Universal input usable for resistance thermometer (RTD), thermocouple (TC), resistance thermometer (Ω), voltage transmitters (mV)
- HART®protocol for converting various input signals to a scalable 4 to 20 mA analog output signal. Operating the transmitter using handheld terminals Field Xpert SFX350/370, field communicator 475 or remotely via PC
- FOUNDATION Fieldbus™ ITK 6.1.2
- PROFIBUS®PA Profile 3.02
- Optional: stainless steel housing for hygienic or Ex d application
- High reliability in harsh industrial environments due to dual compartment housing and compact, fully potted electronics
- Backlit display with large measured value, bar graph and status condition indication
- Diagnostics information according to NAMUR NE107
- International approvals such as FM, CSA (IS, NI, XP and DIP) and ATEX (Ex ia, Ex nA nL, Ex d and dust ignition-proof); marine approval
- SIL certification as per IEC 61508:2010
- Galvanic isolation 2 kV (sensor input / current output)
Specifications
Brand
Measuring Principle
- Field transmitter
Input
- 2 x RTD, TC, Ohm, mV
Output
- 1 x analog 4...20 mA / HART
- FOUNDATION Fieldbus H1
- PROFIBUS PA
Auxiliary Power Supply
- 11.5...42 VDC (HART)
- 11.5...30 VDC (Ex ia)
- 9...32 VDC (FF, PA)
- 10.5...24 VDC (Ex ia, FF, PA)
Communication
- HART
- FOUNDATION Fieldbus
- PROFIBUS PA
Installation
- in field
Accuracy
- (Pt100) <= 0.1 K (HART, FF, PA)
- (Pt100) <= 0.18 °F (HART, FF, PA)
Galvanic Isolation
- yes
Certification
- UL rec. Comp (HART)
- Marine approval only for HART-protocol
- SIL2/3 only for HART-protocol
- ATEX Ex ia, Ex d, Ex tb, Ex ic, Ex nA
- ATEX IECEx Ex tb
- IECEx Ex ia, Ex d, Ex tb
- CSA IS, NI, XP, DIP
- CSA General Purpose
- FM IS, NI, XP, DIP
- FM+CSA XP,DIP, IS, NI
- INMETRO Ex ia, Ex db, Ex tb
- NEPSI Ex ia, Ex nA, Ex d
- EAC Ex ia, Ex d
- UKCA Ex db, Ex ia, Ex nA