iTEMP TMT162 Temperature Transmitter

Brand: Endress+Hauser

iTEMP TMT162 Temperature Transmitter

Brand: Endress+Hauser

Local Support: Authorized Distributor Serving Alabama, Mississippi, Louisiana, Florida, New York, Connecticut, Massachusetts, Vermont, New Hampshire, Maine, Rhode Island, Puerto Rico, US Virgin Islands and parts of Tennessee and Arkansas.

Extended Extended

Unsurpassed reliability, accuracy and long-term stability in critical processes. The remote configurable transmitter transfers and monitors converted signals from RTD sensors and thermocouples as well as from resistance and voltage signals using selectively HART ® , FOUNDATION Fieldbus™-, PROFIBUS ® PA-communication. It visualizes the signals on its own backlit display. A field housing allows a direct connection in harsh process areas as well as in hygienic applications as option.

  • Universal input usable for resistance thermometer (RTD), thermocouple (TC), resistance thermometer (Ω), voltage transmitters (mV)
  • HART®protocol for converting various input signals to a scalable 4 to 20 mA analog output signal. Operating the transmitter using handheld terminals Field Xpert SFX350/370, field communicator 475 or remotely via PC
  • FOUNDATION Fieldbus™ ITK 6.1.2
  • PROFIBUS®PA Profile 3.02
  • Optional: stainless steel housing for hygienic or Ex d application
Features
  • High reliability in harsh industrial environments due to dual compartment housing and compact, fully potted electronics
  • Backlit display with large measured value, bar graph and status condition indication
  • Diagnostics information according to NAMUR NE107
  • International approvals such as FM, CSA (IS, NI, XP and DIP) and ATEX (Ex ia, Ex nA nL, Ex d and dust ignition-proof); marine approval
  • SIL certification as per IEC 61508:2010
  • Galvanic isolation 2 kV (sensor input / current output)

Specifications

Product Family

  • iTEMP

Measuring Principle

  • Field Transmitter

Input

  • 2 x RTD, TC, Ohm, mV

Output

  • 1 x analog 4...20 mA / HART
  • FOUNDATION Fieldbus H1
  • PROFIBUS PA

Auxiliary Power Supply

  • 11.5...42 VDC (HART)
  • 11.5...30 VDC (Ex ia)
  • 9...32 VDC (FF, PA)
  • 10.5...24 VDC (Ex ia, FF, PA)

Communication

  • HART
  • FOUNDATION Fieldbus
  • PROFIBUS PA

Installation

  • in field

Accuracy

  • (Pt100) <= 0.1 K (HART, FF, PA)
  • (Pt100) <= 0.18 °F (HART, FF, PA)

Galvanic Isolation

  • yes

Certification

  • UL rec. Comp (HART)
  • Marine approval only for HART-protocol
  • SIL2/3 only for HART-protocol
  • ATEX Ex ia, Ex d, Ex tb, Ex ic, Ex nA
  • ATEX IECEx Ex tb
  • IECEx Ex ia, Ex d, Ex tb
  • CSA IS, NI, XP, DIP
  • CSA General Purpose
  • FM IS, NI, XP, DIP
  • FM+CSA XP,DIP, IS, NI
  • INMETRO Ex ia, Ex db, Ex tb
  • NEPSI Ex ia, Ex nA, Ex d
  • EAC Ex ia, Ex d
  • UKCA Ex db, Ex ia, Ex nA
show more