Flow-X Flow Computer
Brand: Endress+HauserFlow-X Flow Computer
Brand: Endress+Hauser
The Flow-X flow computer provides gas volume conversion, event logging, parameter logging, and reports using state-of-the-art technology. Identical modules are combined in different housings, offering a multi-stream version Flow-X/P for 1 - 4 measuring distances with a local touch screen, or the version Flow-X/S for smaller installations with one measuring distance. It is the ideal partner for custody transfer gas metering solutions in installations with FLOWSIC600 ultrasonic gas flowmeters.
- Custody gas metering
- Demanding natural gas and process gas applications
Device properties:
- MID approved configuration for gas metering streams with FLOWSIC600
- Powerful modules for demanding applications
- Each module features CPU, memory and equal in/outputs
- Intuitive user interface for graphics display and web browser
- True remote access via Ethernet
- Station computer for multiple streams
- Reduced planning and installation costs through standard configurations
- Very accurate volume conversion with multiple calculation cycles per second
- High reliability through independent modules with their own volume conversion and storage of measured values, counter readings and events
- Easy extension of installations with modules featuring equal in/outputs and 100% software configuration
- Reduced service and maintenance costs with tamper-proof remote maintenance
- Cost-efficient and flexible system integration of multiple streams
Specifications
Brand
Measuring Principle
- flow computer
Measuring Variables
- gas volume conversion, event logging, parameter logging, and reports
Number of Applications
- Support up to 4 gas runs or 2 liquid runs per module (Flow-X/M, Flow-X/C)
Calculations
- Gas property calculations: AGA 5, AGA 8 Part 1, AGA 8 Part 2 (GERG-2008), AGA 10 AGA NX-19; GERG-2008; GERG91mod (GOST 30319.2-1996); GOST 30319.2-2015; GSSSD MR-113; ISO 6976, ISO 12213 Parts 2 and 3; S-GERG
- Flow rate calculations: AGA 3, AGA 7, AGA 9, AGA 11
Electrical Connection
- Current consumption: Flow-X/P0, X/M, X/S: ≤ 0.4 A nominal; ≤ 0.8 A maximal; Flow-X/C: ≤ 0.6 A nominal; ≤ 1.0 A maximal
- Voltage 24 VDC (± 10%), with redundant connections
Ambient Temperature
- Flow-X/S: -40 °C ... +75 °C
- Flow-X/C, Flow-X/P, Flow-X/R: 0 °C ... +60 °C
System
- CPU and memory: 800 MHz, 512 MB RAM, 1 GB flash memory
- Clock: Real-time clock, accuracy better than 1 sec/day
- Gold cap for date and time retention
- Watchdog: Hardware and software watchdog timer
- Tamper switch: Mechanical tamper switch to prevent changing of the application and vital parameters within that application
Supported Gas Chromatographs
- Supports all common gas chromatographs (including ABB NGC8200 series, ABB BTU8100, Danalyser, Yamatake HGC, Encal 3000, Angus GQA, Siemens Maxum and Sitrans)
Conformities
- 2014/32/EU Measuring Instruments Directive (MID)
- Directive 2014/30 / EC relating to electromagnetic compatibility
- 2012/19/EU WEEE Directive (WEEE 2)
- 2011/65/EU RoHS
- OIML R117-1
- WELMEC 7.2, 8.3, 8.8
- API 21.1
Hazardous Area Approvals
- Applies for FlowX/M and X/S only
- Class I, Division 2, Groups A, B, C, and D, T4
- Class I, Zone 2, Group IIC, T4
- IECEx Ex ec IIC Gc
- ATEX II 3 G Ex ec IIC Gc
Inputs
- 6x analog transmitter input, high accuracy
- Input types are 4 to 20 mA, 0 to 20 mA, 0 to 5 V, 1 to 5 V
- Accuracy mA inputs; 0.002% FS at 21 °C, 0.008% at full ambient range of 0-60 °C, long-term stability 0.01% per year
- Resolution: 24 bits. Analog inputs have the same earthing relative to all other electronic devices
- 16x digital status inputs. Resolution 100ns (10MHz)
Outputs
- 4x analog output for process outputs and flow / pressure control. Resolution 14 bits, 0.075% FS
- Analog outputs share same ground floating in relation to all other electronics
- 16x digital output, open collector. Rating 100mA @24V