Capacitance Point Level Detection Liquicap FTI52
Brand: Endress+HauserCapacitance Point Level Detection Liquicap FTI52
Brand: Endress+Hauser
Liquicap FTI52 is a rope probe for point level detection of liquids that are highly viscous and tend to form build-up. Also used for detection of interface and foam of conductive liquids.
Due to its active build-up compensation FTI52 offers maximum reliability and is suited for a wide range of applications thanks to international certificates.
The parts in contact with the process are made of corrosion-resistant and FDA-listed materials - this guarantees a high safety standard.
For liquids that tend to form build-up. Interface detection of different liquids. Two-point control (pump control) with just one process connection. Foam detection of conductive liquids.
- Process connections: Flanges, threads, special hygienic process connections
- Temperature: -80 to +200 °C (-112 to +392 °F)
- Pressure: Vacuum to +100 bar (vacuum to +1,450 psi)
- Sensor length: 12 m (39 ft)
- International explosion protection certificates, overfill prevention WHG, SIL, hygienic certificates, marine approval
- Cost savings thanks to easy and fast commissioning as calibration takes place at the press of a button
- Reliable and safe measurement due to active build-up compensation
- Reliable and universal application thanks to wide range of certificates and approvals
- Short reaction time
- Material in contact with the process made of corrosion-resistant and FDA-listed materials
- Two-stage overvoltage protection
- No need for recalibration after replacing electronics
Specifications
Brand
Measuring Principle
- Capacitive Liquid
Characteristic / Application
- Capacitive Rope probe
Specialities
- Interface detection
- Foam detection
Ambient Temperature
- -50... +70 °C (-58... +158 °F)
- With separate housing: -50... +120 °C (-58... +248 °F)
Process Temperature
- -80... +200 °C (-112... +392 °F)
Process Pressure / Max. Overpressure Limit
- Vacuum...100 bar (1,450 psi)
Main Wetted Parts
- Insulation material: FEP, PFA
- 316L
Process Connection
- G 3/4 ... 1-1/2
- NPT 3/4 ... 1-1/2
- Flange from DN25.../ASME 1".../JIS 10K...
Process Connection Hygienic
- Tri-Clamp ISO2852 gap free plated
- Dairy coupling
- Flush mount
Sensor Length
- Total length of probe: max 12 m (39 ft)
Communication
- 2- wire 19-253 VAC
- 3-wire
- PFM
- Relay DPDT
- DC-PNP
- 8/16 mA
Certificates / Approvals
- ATEX, FM, CSA, CSA C/US, IEC Ex, TIIS, INMETRO, NEPSI, EAC
Safety approvals
- Overfill prevention WHG
- SIL
Design Approvals
- EN 10204-3.1
- NACE MR0175
Marine Approval
- GL/ ABS/ DNV
Options
- Inactive length
- Active build-up compensation
- Separate housing
Components
- Transmitter
- PFM: FTC325, FTC625, FTC470Z, FTC471Z
- 3-wire: FTC325
Application Limits
- Notice the pressure and temperature derating
- Notice for non conductive medium the DK