Conductive Point Level Detection Liquipoint FTW33
Brand: Endress+HauserConductive Point Level Detection Liquipoint FTW33
Brand: Endress+Hauser
The Liquipoint FTW33 is developed for the food industry and meets all international hygiene requirements. The device also fits perfectly for applications in all industries. For use in pasty and sticky media and media with heavy build-up.
For use in pipes and in storage, mixing and process vessels with or without an agitator. For liquids with electrical conductivity >1 μS/cm or dielectric constant >2.
Developed for the food industry. Detection of foam occurring within the food industry possible.
- Process connections: Threads and hygiene connections
- Sensor length: Flush-mounted
- Temperature: -20 to +100°C (-4 to +212°F), CIP/SIP to 150°C (302°F) for 1 hour
- Pressure: 0 to 25bar abs (0 to 362,5psi abs)
- Hygienic certificates
- Perfect fit to the hygienic industry thanks to flush-mounted design, which allows pigging of pipes
- Safe and reliable measurement due to build-up compensation, ensuring reliable switching; IO-Link reduces costs and complexity due to easy configuration and flexible integration in all fieldbus systems
- Individual adjustment to each medium not necessary
- Easy installation thanks to compact design, even in tight conditions or where access is restricted
- Broad range of process connections for installation in new and existing plants
- CIP and SIP cleanability ensured - up to protection class IP 69
- LED display for on-site function check
Specifications
Brand
Measuring Principle
- Conductive
Characteristic / Application
- Compact point level switch for using in pipes and in storage, mixing and process vessels with or without an agitator, for water based or oil based media, with active build up compensation, flush mounting
Specialities
- CIP and SIP suitable
- Conductive foam is detectable or can be switched off
Supply / Communication
- 10…30 VDC
Ambient Temperature
- -40 ... 70°C
- -40 ... 158°F
Process Temperature
- Cleaning: -20 ... 150°C (-4 ... 302°F) for 1h
- Standard: -20 ... 100°C
Process Pressure / Max. Overpressure Limit
- Vacuum ... 25 bar
- Vacuum ... 362,5 psi
Main Wetted Parts
- Sensor: 316L
- Sensor isolation: PEEK
Process Connection
- Thread G1, G1/2, G3/4, M24
Process Connection Hygienic
- Clamp ISO 2852 1 to 1-1/2", 2"
- DIN11851 Pipe union
Communication
- DC PNP
Certificates / Approvals
- CSA C/US
Design Approvals
- EN 10204-3.1
Hygienic Approvals
- 3A, EHEDG
Options
- Weld-in adapter
- Process adapter for hygienic process connections