RLN22 NAMUR Isolating Amplifier

Brand: Endress+Hauser

RLN22 NAMUR Isolating Amplifier

Brand: Endress+Hauser
Fundamental Fundamental

The RLN22 is a compact 1- or 2-channel, 24 V DC isolating amplifier with relay signal output. It is designed to safely operate e.g. proximity sensors or point level switches such as the Liquiphant FTL51B (NAMUR) as per IEC 60947-5-6. The DC interface monitors line faults such as breaks or short-circuits of sensors or mechanical switching contacts. The device is suited for use in hazardous areas and safety instrumented systems up to SIL 2 in accordance with IEC 61508.

  • Isolating amplifier for the transmission of binary switching signals
  • Input for proximity sensors, open contacts or contacts with resistive coupling elements
  • Galvanic isolation (3-way)
  • Line fault monitoring of input circuits or mechanical switching contacts
  • Group error message via DIN rail bus connector
  • Output-side relay contacts, direction of action (operating or quiescent current behavior) via DIP switch selection
  • Ambient temperature range: –40 to 60 °C (–40 to 140 °F)
Features
  • Safe and reliable switching operations: trust your critical applications
  • Compact housing: up to 2 channels on 12.5 mm (0.49 in) for efficient use of space in control cabinets
  • Installation in hazardous areas; Ex approval for Ex zone 2
  • Up to SIL 2 in accordance with IEC 61508
  • Quick and easy wiring and commissioning: plug-in terminals, power supply and group error message module via DIN rail bus connector

Specifications

Measuring Principle

  • Active barrier

Function

  • 1-channel, changeover contact
  • 2-channel, normally open contact

Loop Power Supply

  • 8 VDC

Power Supply

  • 24 VDC

Auxiliary Power Supply / Loop Power Supply

  • 8 VDC

Input

  • NAMUR
  • blocking: 2.1 mA

Output

  • relay contact

Certificates

  • ATEX IECEx II(1)G [Ex ia Ga] IIC, II(1) D [Ex ia Da] IIIC, II3G Ex ec nC IIC Gc
  • DNV

SIL

  • SIL 2

Operation

  • DIP switch
show more