RLN22 NAMUR Isolating Amplifier
Brand: Endress+HauserRLN22 NAMUR Isolating Amplifier
Brand: Endress+Hauser
The RLN22 is a compact 1- or 2-channel, 24 V DC isolating amplifier with relay signal output. It is designed to safely operate e.g. proximity sensors or point level switches such as the Liquiphant FTL51B (NAMUR) as per IEC 60947-5-6. The DC interface monitors line faults such as breaks or short-circuits of sensors or mechanical switching contacts. The device is suited for use in hazardous areas and safety instrumented systems up to SIL 2 in accordance with IEC 61508.
- Isolating amplifier for the transmission of binary switching signals
- Input for proximity sensors, open contacts or contacts with resistive coupling elements
- Galvanic isolation (3-way)
- Line fault monitoring of input circuits or mechanical switching contacts
- Group error message via DIN rail bus connector
- Output-side relay contacts, direction of action (operating or quiescent current behavior) via DIP switch selection
- Ambient temperature range: –40 to 60 °C (–40 to 140 °F)
- Safe and reliable switching operations: trust your critical applications
- Compact housing: up to 2 channels on 12.5 mm (0.49 in) for efficient use of space in control cabinets
- Installation in hazardous areas; Ex approval for Ex zone 2
- Up to SIL 2 in accordance with IEC 61508
- Quick and easy wiring and commissioning: plug-in terminals, power supply and group error message module via DIN rail bus connector
Specifications
Brand
Measuring Principle
- Active barrier
Function
- 1-channel, changeover contact
- 2-channel, normally open contact
Loop Power Supply
- 8 VDC
Power Supply
- 24 VDC
Auxiliary Power Supply / Loop Power Supply
- 8 VDC
Input
- NAMUR
- blocking: 2.1 mA
Output
- relay contact
Certificates
- ATEX IECEx II(1)G [Ex ia Ga] IIC, II(1) D [Ex ia Da] IIIC, II3G Ex ec nC IIC Gc
- DNV
SIL
- SIL 2
Operation
- DIP switch